Findings: SCADAPack STAT-LED blinking in Red signal.
Action Taken: Restart the SCADAPack & radio modem.





Findings: SCADAPack STAT-LED blinking in Red signal.
Action Taken: Restart the SCADAPack & radio modem.





Findings: 1. Optical fiber are found damaged. Action Taken: 1. OTDR test . Cable disconnect at 0.7634 km. 2. Physically cable & TJ…
Findings: Function Generator doesn’t work properly. Action Taken: 1. Physically check the connection 2. Check the pulse signal from SCADAPACK & pulse generator….
Findings: FIT-4002 Ultrasonic sensor Schedule maintenance time over ., Action taken: Plug out both Upstream & Downstream sensor. Clean the sensor & cable…
Findings: Communication isn’t occurred in GiMAC meter. Action taken: 1. Physically check. Checked by modbuspool. GiMAC meter comm. Port has problem. Only transmit…