DTW114 Local Pipeline MOV-1 automatic close when MOV-1 turn in Remote mode
Checking Step SL Checking Stage Remarks MOV physical status (Wiring, OK 1 MOV to RTU Panel Terminal MOV ok. 2 SCADAPACK Analog output…
PWTP Micro SCADA
SL. No Name/Brand Model Location Type Remarks 01 CONSERVER WXD216NCR PWTP/IPS/BPS Micro SCADA 02 Ethernet Switch H3C S1016/1024 PWTP/IPS/BPS Switch 03 04 05…
LS Electronic Motor Protection Relay (DMP60-TZ)
Brand Name: LS Product Name: Electronic Motor Protection Relay Model No/Part No: DMP60-TZ SPECIFICATION OF LS Electronic Motor Protection Relay (DMP60-TZ) SL NO….
WID585:Dtw-117 e-PRV CRD isn’t functioning properly. SEL manpower need to check.Now e-PRV CRD & flowmeter works
26.11.2023 Today SEL manpower change the e-PRV CRD spring. And we check the e-PRV functionality is okay or not okay. MOV-1 50% Open,…
WID597: Dtw-101 PIT value isn’t shown in SCADA .
Findings: PIT internal CKT damaged found. Action Taken: Install new pressure transmitter.
WID558: DTW123 ELD installation and Leakage current check.
Findings : ELD fuse burns when main UPS take input power. Action taken: 1. UPS replace but problem isn’t solved. 2. ELD replace…