IRP-2 All ultrasonic type level sensor clean task complete.



স্লাজ ড্রায়িং বেডের পানি, পাম্প চেম্বারের লেভেল পূর্ণ করতে সময় বেশি নেয়।
Findings: 1. Always PWP panel inverter fault is showing. 2. Magnetic Contact coil damaged found. Action Taken: Magnetic contact change.
Action Taken: 1. Check SPD. 2. Check Antenna cable. 3. Checking the RSSI value changing the direction of Antenna. Result: After doing the…
Finding: MOV 2V07-L opening & closing time percentage isn’t showing properly in SCADA & Field side. Action Taken: Reset the MOV-2V07.
The DTW106 has been constructed recently. GKB engineering Ltd. got the electrical and scada integration work. Before handover ICE-Team has been engaged to…