WID594: Dtw-203 Radio communication error. Need to check.
Findings: SCADAPack STAT-LED blinking in Red signal. Action Taken: Restart the SCADAPack & radio modem.
WID602: Dtw-103 VFD fault. It happened also the previous 5 times. Need to properly check ups and others all panel.
Findings: Serial comm. cable lose connection found & generator has Digital Input fault problem that’s why modbus interrupt comes frequently. Action taken: Plugout…

LIT sensor cleaning
IRP-2 All ultrasonic type level sensor clean task complete.
WID599:DTW-121 serial communication problem. Need to check.
Findings: The radio antenna signal can’t pass due to tree. Action Taken: Increase Antenna height. Clean connectors & terminals. Restart the modem. Before…