| Brand Name: | Weidmuller | 
| Product Name: | Switch-mode power supply | 
| Model No/Part No: | PRO ECO 240W 24V 10A | 
| Country of Origin: | |
| Country of Shipment: | As per country of origin | 
| SL No | Specification criteria | Specifications | 
|---|---|---|
| 1 | Type | PRO ECO 240W 24V 10A | 
| 2 | Version | Power supply, switch-mode power supply unit, 24 V | 
| 3 | Width | 60 mm | 
| 4 | Width (inches) | 2.362 inch | 
| 5 | Height | 125 mm | 
| 6 | Height (inches) | 4.921 inch | 
| 7 | Depth | 100 mm | 
| 8 | Depth (inches) | 3.937 inch | 
| 9 | Net weight | 1,055 g | 
| 10 | Operating temperature | -25 °C…70 °C | 
| 11 | Storage temperature | -40 °C…85 °C | 
| 12 | AC current consumption | 1,23 A @ 230 V AC / 2,47 A @ 110 V AC | 
| 13 | AC input voltage range | 85…264 V AC (Derating @ 100 V AC) | 
| 14 | Connection system | Screw connection | 
| 15 | DC current consumption | 1,18 A @ 370 V DC / 2,4 A @ 120 V DC | 
| 16 | DC input voltage range | 80…370 V DC (Derating @ 120 V DC) | 
| 17 | Frequency range AC | 47…63 Hz | 
| 18 | Input frequency | 47…63 Hz | 
| 19 | Input fuse (internal) | Yes | 
| 20 | Inrush current | max. 15 A | 
| 21 | Rated input voltage | 100…240 V AC (wide-range input) 4 A / DI, safety fuse | 
| 22 | Recommended back-up fuse | 10 A, Char. B, circuit breaker 3…4 A, Char. C, circuit breaker | 
| 23 | Capacitive load | unrestricted | 
| 24 | Connection system | Screw connection | 
| 25 | Continuous output current @ URated | 10 A @ 55 °C, 7.5 A @ 70 °C | 
| 26 | Output power | 240 W | 
| 27 | Output voltage | 24 V | 
| 28 | Output voltage | 22…28 V (adjustable via potentiometer) | 
| 29 | Overload protection | Yes | 
| 30 | Parallel connection option | yes, max. 5 | 
| 31 | Protection against inverse voltage | Yes | 
| 32 | Ramp-up time | ≤ 100 ms | 
| 33 | Rated (nominal) output current @ UNom | 10 A @ 55 °C | 
| 34 | Rated output voltage | 24 V DC ± 1 % | 
| 35 | Residual ripple, breaking spikes | < 50 mVSS @ 24 V DC, IN | 
| 36 | AC failure bridging time @ INom | 20 ms @ 230 V AC / > 20 ms @ 115 V AC | 
| 37 | Degree of efficiency | 90% | 
| 38 | Earth leakage current, max | 3.5 mA | 
| 39 | Housing version | Metal, corrosion resistant LED green (Uoutput > 21.6 V DC), LED yellow (Ioutput > 90% IRated typ. ), LED red | 
| 40 | Indication | yellow (Ioutput > 90% IRated typ. ), LED red (overload, overtemperature, short-circuit, Uoutput < 20.4 V DC) | 
| 41 | MTBF | 500,000 h acc. to IEC 1709 (SN29500 | 
| 42 | Max. perm. air humidity (operational) | 5 %…95 % RH | 
| 43 | Mounting position, installation notice | on terminal rail TS 35 | 
| 44 | Operating temperature | -25 °C…70 °C | 
| 45 | Power factor (approx.) | 0.94 @ 230 V AC / > 0.99 @ 115 V AC | 
| 46 | Power loss, idling | 3 W | 
| 47 | Power loss, nominal load | 24 W | 
| 48 | Protection against over-heating | Yes | 
| 49 | Protection against reverse voltages from the load | 30…35 V DC | 
| 50 | Protection degree | IP20 | 
| 51 | Short-circuit protection | Yes | 
| 52 | Limiting of mains voltage harmonic currents | in accordance with EN 61000-3-2 | 
| 53 | Noise emission acc. to EN55022 | Class A | 
| 54 | Vibration resistance IEC 60068-2-6 | 1 g according to EN50178 EN 61000-4-2 (ESD), EN 61000-4-3 (RS), EN 61000-4-4 (burst), EN 61000-4-5 | 
| 55 | Interference immunity test acc. to | (surge), EN 61000-4-6 (conducted), EN61000-4-8 (Fields), EN61000-4-11 (Dips) | 
| 56 | Shock resistance IEC 60068-2-27 | 15 g In all directions | 
| 57 | Class of protection | I, with PE connection | 
| 58 | Insulation voltage input / earth | 2 kV | 
| 59 | ||
| 60 | Insulation voltage output / earth | 0.5 kV | 
| 61 | Insulation voltage, input/output | 3 kV | 
| 62 | Pollution severity | 2 | 
| 63 | Electrical machine equipment | Acc. to EN60204 | 
| 64 | For use with electronic equipment | Acc. to EN50178 / VDE0160 | 
| 65 | Protection against dangerous shock currents | Acc. to VDE0106-101 | 
| 66 | Protective separation / protection against electrical shock | VDE0100-410 / acc. to DIN57100-410 | 
| 67 | Safety extra-low voltage | SELV acc. to EN60950, PELV acc. to EN60204 | 
| 68 | Safety transformers for switch-mode power supplies | nach EN61558-2-16 | 
| 69 | Contact load (NO contact) | max. 30 V DC / 1 A | 
| 70 | Floating contact | Yes | 
| 71 | Relay on/off | Output voltage >21.6 V DC/ <20.4 V DC, Overload | 
| 72 | Descriptive text ordering data | The internal varistor found in a switchmode power supply does not replace the need for surge protection within a system. | 

 
			