ACTIVITY | DAILY REPORTS | DTW | Pappu | ParvezDTW-110 Pump inspection & ready to run up.
Posted onProblem Found: 1. VFD (-) Hz showing 2. Non-return Valve damaged. 3. Reverse water flow. 4. The pump acts as a generator due…
- DAILY REPORTS | DTW | Parvez
WID577: DTW-204 ACB can not close from SCADA.
Posted onFindings: UVR being under voltage, it need a reset to execute Close Command. Action: ACB open/close command relay check. Isolate the physical reset…
WID550: DTW-207 optical fiber maintenance.
Posted onFindings: Lots of hanging TJ box is visiable. Action Taken: Reduce TJ box replacing optical fiber.
ACTIVITY | DAILY REPORTS | DTW | Parvez | REPORTSDTW-211 CCTV power is taken from main ups
Posted onDTW-211 CCTV power is taken from main ups. Do not get sufficient backup from ups and frequently fault occurs.
ACTIVITY | DAILY REPORTS | Parvez | REPORTSBreaker installation for SCADA control Room Monitor.
Posted onBreaker installation for SCADA control Room Monitor Done