Problem: after power up time ACB do not close from the SCADA command.
Problem found: 27X M/C Magnetic Contact & AUX CONTACT UNIT Problem found.
Observation: DTW 113 UVR checked, When plug PTT UVR give contact with (207V) and 27x relay didn’t energize, 27x relay coil problem. 27x relay remove and bring it to store.