Due to solving those problems :
- Modbus ground connection check.
- VFD frequency regulator loose connection check.
- SPD check .
- RJ-45 connector check.
- Cable check.
- VFD controller Check.
- System Earth Resistance Check etc.
Due to solving those problems :
Modbus Serial communication cable check Complete. No problem Found in the Field LIT Do Not Down in The Boring After 10 Meter
Problem: after power up time ACB do not close from the SCADA command. Problem found: 27X Magnetic Contact (M/C) & AUX Contact Unit…