PIT Maintenance Work Report (IRP-1)
DTW-114 PIT ok. DTW-113 PIT ok but scadapack AO port damaged. DTW-104 PIT doesn’t exist. DTW-105 PIT ok (regeneration on going)
CCTV Maintenance At DTW-219
1 new camera installation 2. UTP cable change 3. Connector change 4. IP Setting 5. IP Seating
WID577: DTW-204 ACB can not close from SCADA.
Findings: UVR being under voltage, it need a reset to execute Close Command. Action: ACB open/close command relay check. Isolate the physical reset…
OGR booster pump F MOV limit switch adjustment complete.
Problem: When the pump is stopped and normally shuts off, a fault automatically occurs in the mov. In this case the valve is…
OGR Booster pump E checking & maintenance.
Problem: OGR Booster pump E running time Moter current high (682 Amp) showing than pump stop that time frequency is 0.3 Hz (Abnormal).Problem…
DTW 117 PIT Checking and maintenance complete.
Problem: PIT value does not showing in the SCADA & field device.Problem found: PIT 24v AC supply fuse damage found & maintenance. now…