DTW 104 CCTV maintenance complete.
ACTIVITY | CCTV | DAILY REPORTS | DTW | Jewel

DTW 104 CCTV maintenance complete.

Posted onOctober 10, 2022October 10, 2022

Problem: 01 nos CC Camera Do not show footage in NAV.Problem found: Automatic IP has been changed in the dome Camera. Than IP…

Listen to the Message DTW 104 CCTV maintenance complete.Continue

DTW 117 PIT Checking and maintenance complete.
ACTIVITY | DAILY REPORTS | DTW | Pappu

DTW 117 PIT Checking and maintenance complete.

Posted onOctober 10, 2022October 10, 2022

Problem: PIT value does not showing in the SCADA & field device.Problem found: PIT 24v AC supply fuse damage found & maintenance. now…

Listen to the Message DTW 117 PIT Checking and maintenance complete.Continue

DTW- 114 UVR & UVR Related M/C checking complete.
ACTIVITY | DAILY REPORTS | DTW | Pappu | Pending Issue

DTW- 114 UVR & UVR Related M/C checking complete.

Posted onOctober 10, 2022October 11, 2022

Problem: after power up time ACB do not close from the SCADA command.Problem found: DTW 114 UVR its burn inside circuit . UVR…

Listen to the Message DTW- 114 UVR & UVR Related M/C checking complete.Continue

DTW- 113 UVR & UVR Related M/C checking complete.
ACTIVITY | DAILY REPORTS | DTW | Pappu | Pending Issue

DTW- 113 UVR & UVR Related M/C checking complete.

Posted onOctober 10, 2022October 11, 2022

Problem: after power up time ACB do not close from the SCADA command.Problem found: 27X M/C Magnetic Contact & AUX CONTACT UNIT Problem…

Listen to the Message DTW- 113 UVR & UVR Related M/C checking complete.Continue

DTW 203 UVR checking complete.
ACTIVITY | DAILY REPORTS | DTW | Pappu | Pending Issue

DTW 203 UVR checking complete.

Posted onOctober 10, 2022October 11, 2022

Problem: Shutdown time is ACB not open.Problem found: ACB Internal control unit not working found.Observation: DTW 203 UVR checked, When plug PTT UVR…

Listen to the Message DTW 203 UVR checking complete.Continue

Unused & damage LIT sensor collects complete   from DTW 105,106,115,203 & 212
ACTIVITY | DAILY REPORTS | DTW | Pappu

Unused & damage LIT sensor collects complete from DTW 105,106,115,203 & 212

Posted onOctober 10, 2022October 10, 2022

Unused & damage LIT sensor collects complete from DTW 105 – 1 nos DTW 106 – 1 nos & new lit sensor install.DTW…

Listen to the Message Unused & damage LIT sensor collects complete from DTW 105,106,115,203 & 212Continue

IRP-2 3V07A MOV Reset, reprogramming and configuration work complete.
ACTIVITY | DAILY REPORTS | MOV | Pappu | Parvez

IRP-2 3V07A MOV Reset, reprogramming and configuration work complete.

Posted onOctober 6, 2022October 6, 2022

Problem: This MOV is abnormal working. MOV Open time & close time 0% to 100% value not showing. IRP-2 3V07A MOV Reset, reprogramming…

Listen to the Message IRP-2 3V07A MOV Reset, reprogramming and configuration work complete.Continue

Radio communication checking complete DTW 221.
ACTIVITY | DAILY REPORTS | DTW | NETWORK CONNECTIVITY | Pappu | Pending Issue

Radio communication checking complete DTW 221.

Posted onOctober 6, 2022October 12, 2022

Observation: Radio communication checking complete DTW 221.1. In DTW 221, We checked up to 10 minutes. RSSI Value (Dc volts) MAX: 2.700V, MIN:…

Listen to the Message Radio communication checking complete DTW 221.Continue

Radio communication checking complete DTW 213.
ACTIVITY | DAILY REPORTS | DTW | NETWORK CONNECTIVITY | Pappu | Pending Issue

Radio communication checking complete DTW 213.

Posted onOctober 6, 2022October 12, 2022

Observation: Radio communication checking complete DTW 213.1. In DTW 213, We checked up to 10 minutes. RSSI Value (Dc volts) MAX: 2.395V, MIN:…

Listen to the Message Radio communication checking complete DTW 213.Continue

UVR checking complete at DTW 216
ACTIVITY | DAILY REPORTS | DTW | Pappu | Pending Issue

UVR checking complete at DTW 216

Posted onOctober 6, 2022October 12, 2022

Problem: Shutdown time is ACB not open.Problem found: ACB Internal control unit not working found.Observation: DTW 216 UVR checked, when plug PTT UVR…

Listen to the Message UVR checking complete at DTW 216Continue