DTW’S PRESSURE INDICATOR TRANSMITTER REPORT
SAVAR-KERANIGANJ WELL FIELD PLANT DTW,S PRESSURE INDICATOR TRANSMITTER REPORT (24.09.2022) DTW NO. VALUE STATUS DTW NO. VALUE STATUS 101 2.3 OK 201 1.9…
Problem: after power up time ACB do not close from the SCADA command. Problem found: 27X Magnetic Contact (M/C) & AUX Contact Unit…
Problem: OGR Booster pump E running time Moter current high (682 Amp) showing than pump stop that time frequency is 0.3 Hz (Abnormal).Problem…
Problem: Do not show footage in NAV.Problem found: ONU & 1 Nos cc camera Problem found.
1 :MW03B 2: MW14A 3:MW08A 4: MW13B
Problem: In those sensors, high temperature shows in transmitter display. But when we check the mA current of sensor signal, that was OK….
Problem: SCADA always showing HI signal. Problem found: 1 NOS float switch problem found. A good sensor in HIHI position is replaced with…
Problem Found: 1. VFD (-) Hz showing 2. Non-return Valve damaged. 3. Reverse water flow. 4. The pump acts as a generator due…
Problem: SCADA always showing HI signal. Problem found: 1 Nos float switch problem. HI signal float switch problem & float switch connection terminal…
Problem found: lode shell connection terminal circuit problem found.