    WID616: DTW-107 LIT, PIT, FIT isolation due to regeneration work.

    Posted onDecember 31, 2023December 31, 2023

    Due to regeneration work, We disconnect the connection of LIT, PIT, FIT.

    Listen to the Message WID616: DTW-107 LIT, PIT, FIT isolation due to regeneration work.Continue

  • Uncategorized

    WID617: DTW-111, 1 Nos repaired camera installation .

    Posted onDecember 31, 2023December 31, 2023

    After being damaged the camera, We collect it and replace a good circuit with damaged circuit.

    Listen to the Message WID617: DTW-111, 1 Nos repaired camera installation .Continue

  • Uncategorized

    WID599:DTW-121 serial communication problem. Need to check.

    Posted onDecember 19, 2023December 19, 2023

    Findings: The radio antenna signal can’t pass due to tree. Action Taken: Increase Antenna height. Clean connectors & terminals. Restart the modem. Before…

    Listen to the Message WID599:DTW-121 serial communication problem. Need to check.Continue

  • Uncategorized

    WID606: IRP-01, S/F Bed A to D Suddenly becomes local mode and LIT level is 0.00 (A-D) Showing in SCADA. Need to check emergency ice team.

    Posted onDecember 19, 2023December 19, 2023

    Listen to the Message WID606: IRP-01, S/F Bed A to D Suddenly becomes local mode and LIT level is 0.00 (A-D) Showing in SCADA. Need to check emergency ice team.Continue

  • Uncategorized

    WID605: Dtw-203, 206 Radio Communication problems. Need to check. Now pump is locally running.

    Posted onDecember 14, 2023December 14, 2023

    Findings: Radio Modem become hang. Action taken: Restart the Modem.

    Listen to the Message WID605: Dtw-203, 206 Radio Communication problems. Need to check. Now pump is locally running.Continue

  • Uncategorized

    WID602: Dtw-103 VFD fault. It happened also the previous 5 times. Need to properly check ups and others all panel.

    Posted onDecember 14, 2023December 19, 2023

    Findings: Serial comm. cable lose connection found & generator has Digital Input fault problem that’s why modbus interrupt comes frequently. Action taken: Plugout…

    Listen to the Message WID602: Dtw-103 VFD fault. It happened also the previous 5 times. Need to properly check ups and others all panel.Continue

  • Uncategorized

    WID601: FIT4002 value is fluctuating too much… which is unusual… need urgent checking.

    Posted onDecember 14, 2023December 14, 2023

    Findings: FIT-4002 Ultrasonic sensor Schedule maintenance time over ., Action taken: Plug out both Upstream & Downstream sensor. Clean the sensor & cable…

    Listen to the Message WID601: FIT4002 value is fluctuating too much… which is unusual… need urgent checking.Continue

  • Uncategorized

    প্রয়োজনীয় মালামাল ও জরূরী তালিকা(অর্থ বৎসর ২৩-২৪)

    Posted onDecember 11, 2023January 15, 2024

    প্রয়োজনীয় মালামাল ও জরূরী তালিকা স্ক্যাডা সম্পর্কিত – অর্থ বৎসর ২৩-২৪ সিরিয়াল নং নাম পরিমান রেফারেন্স / মন্তব্য 1 Mikrotik Router (Model –…

    Listen to the Message প্রয়োজনীয় মালামাল ও জরূরী তালিকা(অর্থ বৎসর ২৩-২৪)Continue

  • Uncategorized

    WID604: Chlorinator -3 servicing work with Mechanical Team.

    Posted onDecember 11, 2023December 11, 2023

    Cable connection: Red-RedRed/white-BlackGreen/white-WhiteGreen-GreenBlack- Black/whiteYellow-Yellow/whiteBlue-Green/white

    Listen to the Message WID604: Chlorinator -3 servicing work with Mechanical Team.Continue

  • Uncategorized

    WID603: Monitoring Well Data collection & sensor maintenance.

    Posted onDecember 11, 2023December 14, 2023

    Listen to the Message WID603: Monitoring Well Data collection & sensor maintenance.Continue