Skip to content
TEAM ICE
  • Home
  • ICE LAB
  • Product Specifications
  • Technical Papers
TEAM ICE
  • Uncategorized

    WID616: DTW-107 LIT, PIT, FIT isolation due to regeneration work.

    Posted onDecember 31, 2023December 31, 2023

    Due to regeneration work, We disconnect the connection of LIT, PIT, FIT.

    Listen to the Message WID616: DTW-107 LIT, PIT, FIT isolation due to regeneration work.Continue

  • Uncategorized

    WID617: DTW-111, 1 Nos repaired camera installation .

    Posted onDecember 31, 2023December 31, 2023

    After being damaged the camera, We collect it and replace a good circuit with damaged circuit.

    Listen to the Message WID617: DTW-111, 1 Nos repaired camera installation .Continue

  • Uncategorized

    DTW-218,2106,214,215,213 RTU,CCTV  Panel and VFD Cleaning

    Posted onDecember 21, 2023December 21, 2023

    Listen to the Message DTW-218,2106,214,215,213 RTU,CCTV  Panel and VFD CleaningContinue

  • Uncategorized

    WID599:DTW-121 serial communication problem. Need to check.

    Posted onDecember 19, 2023December 19, 2023

    Findings: The radio antenna signal can’t pass due to tree. Action Taken: Increase Antenna height. Clean connectors & terminals. Restart the modem. Before…

    Listen to the Message WID599:DTW-121 serial communication problem. Need to check.Continue

  • Uncategorized

    WID606: IRP-01, S/F Bed A to D Suddenly becomes local mode and LIT level is 0.00 (A-D) Showing in SCADA. Need to check emergency ice team.

    Posted onDecember 19, 2023December 19, 2023

    Listen to the Message WID606: IRP-01, S/F Bed A to D Suddenly becomes local mode and LIT level is 0.00 (A-D) Showing in SCADA. Need to check emergency ice team.Continue

  • ACTIVITY | Uncategorized

    DTW-109,110,111,113,114,115 RTU,CCTV Panel and VFD Cleaning

    Posted onDecember 18, 2023December 18, 2023

    Listen to the Message DTW-109,110,111,113,114,115 RTU,CCTV Panel and VFD CleaningContinue

  • Uncategorized

    WID605: Dtw-203, 206 Radio Communication problems. Need to check. Now pump is locally running.

    Posted onDecember 14, 2023December 14, 2023

    Findings: Radio Modem become hang. Action taken: Restart the Modem.

    Listen to the Message WID605: Dtw-203, 206 Radio Communication problems. Need to check. Now pump is locally running.Continue

  • Uncategorized

    WID602: Dtw-103 VFD fault. It happened also the previous 5 times. Need to properly check ups and others all panel.

    Posted onDecember 14, 2023December 19, 2023

    Findings: Serial comm. cable lose connection found & generator has Digital Input fault problem that’s why modbus interrupt comes frequently. Action taken: Plugout…

    Listen to the Message WID602: Dtw-103 VFD fault. It happened also the previous 5 times. Need to properly check ups and others all panel.Continue

  • Uncategorized

    WID601: FIT4002 value is fluctuating too much… which is unusual… need urgent checking.

    Posted onDecember 14, 2023December 14, 2023

    Findings: FIT-4002 Ultrasonic sensor Schedule maintenance time over ., Action taken: Plug out both Upstream & Downstream sensor. Clean the sensor & cable…

    Listen to the Message WID601: FIT4002 value is fluctuating too much… which is unusual… need urgent checking.Continue

  • Uncategorized

    প্রয়োজনীয় মালামাল ও জরূরী তালিকা(অর্থ বৎসর ২৩-২৪)

    Posted onDecember 11, 2023January 15, 2024

    প্রয়োজনীয় মালামাল ও জরূরী তালিকা স্ক্যাডা সম্পর্কিত – অর্থ বৎসর ২৩-২৪ সিরিয়াল নং নাম পরিমান রেফারেন্স / মন্তব্য 1 Mikrotik Router (Model –…

    Listen to the Message প্রয়োজনীয় মালামাল ও জরূরী তালিকা(অর্থ বৎসর ২৩-২৪)Continue

Page navigation

Previous PagePrevious 1 … 3 4 5 6 7 … 20 Next PageNext

Dhaka Water Supply and Sewerage Authority

+88 01797187749

Join With Us

© 2025 TEAM ICE

  • Home
  • ICE LAB
  • Product Specifications
  • Technical Papers