WID597: Dtw-101 PIT value isn’t shown in SCADA .
Findings: PIT internal CKT damaged found. Action Taken: Install new pressure transmitter.
WID599: DTW-121 serial communication problem. Need to check.
Findings: 1. Always PWP panel inverter fault is showing. 2. Magnetic Contact coil damaged found. Action Taken: Magnetic contact change.
WID594: Dtw-203 Radio communication error. Need to check.
Findings: SCADAPack STAT-LED blinking in Red signal. Action Taken: Restart the SCADAPack & radio modem.
WID590: IRP-1 OGR utility pump problem check.IRP-1 OGR utility pump problem check.
Findings: Switch problem found. Action taken: Switch replace.
WID587: DTW115 GiMAC values isn’t shown in SCADA.
Findings: Communication isn’t occurred in GiMAC meter. Action taken: 1. Physically check. Checked by modbuspool. GiMAC meter comm. Port has problem. Only transmit…
WID590: IRP-1 OGR utility pump problem check.
Findings: Flote Switch mis-displacement problem found. Need to dressing the cable with cable tie.
WID586: DTW-104 VFD fault & Modbus communication interruption. Need to check.
Findings: 1. Signal Cable problem. 2. GiMAC Rx & Rt port problem found. Action Taken: 1. Cable check. 2. VFD controller port check…