WID603: Monitoring Well Data collection & sensor maintenance.

Posted onDecember 11, 2023December 14, 2023

Listen to the Message WID603: Monitoring Well Data collection & sensor maintenance.Continue

Uncategorized

WID600: IRP-1 & IRP-2 GCP & PLC Communication check list

Posted onDecember 10, 2023December 10, 2023

SL No. DTW No. Serial Comm. Condition Generator Battery Cable Remarks 01 101 Okay Okay Okay   02 102 Okay Okay Okay  …

Listen to the Message WID600: IRP-1 & IRP-2 GCP & PLC Communication check listContinue

Uncategorized

DTW-219,220,221,222,223 RTU and CCTV PANEL CLEANING

Posted onDecember 5, 2023December 5, 2023

Listen to the Message DTW-219,220,221,222,223 RTU and CCTV PANEL CLEANINGContinue

Uncategorized

WID597: Dtw-101 PIT value isn’t shown in SCADA .

Posted onDecember 4, 2023December 4, 2023

Findings: PIT internal CKT damaged found. Action Taken: Install new pressure transmitter.

Listen to the Message WID597: Dtw-101 PIT value isn’t shown in SCADA .Continue

Uncategorized

WID599: DTW-121 serial communication problem. Need to check.

Posted onDecember 4, 2023December 4, 2023

Findings: 1. Always PWP panel inverter fault is showing. 2. Magnetic Contact coil damaged found. Action Taken: Magnetic contact change.

Listen to the Message WID599: DTW-121 serial communication problem. Need to check.Continue

Uncategorized

WID594: Dtw-203 Radio communication error. Need to check.

Posted onDecember 3, 2023December 3, 2023

Findings: SCADAPack STAT-LED blinking in Red signal. Action Taken: Restart the SCADAPack & radio modem.

Listen to the Message WID594: Dtw-203 Radio communication error. Need to check.Continue

Uncategorized

WID590: IRP-1 OGR utility pump problem check.IRP-1 OGR utility pump problem check.

Posted onNovember 28, 2023December 11, 2023

Findings: Switch problem found. Action taken: Switch replace.

Listen to the Message WID590: IRP-1 OGR utility pump problem check.IRP-1 OGR utility pump problem check.Continue

Uncategorized

WID587: DTW115 GiMAC values isn’t shown in SCADA.

Posted onNovember 28, 2023December 11, 2023

Findings: Communication isn’t occurred in GiMAC meter. Action taken: 1. Physically check. Checked by modbuspool. GiMAC meter comm. Port has problem. Only transmit…

Listen to the Message WID587: DTW115 GiMAC values isn’t shown in SCADA.Continue

Uncategorized

WID590: IRP-1 OGR utility pump problem check.

Posted onNovember 28, 2023November 28, 2023

Findings: Flote Switch mis-displacement problem found. Need to dressing the cable with cable tie.

Listen to the Message WID590: IRP-1 OGR utility pump problem check.Continue

Uncategorized

PWID52:DTW201 to 205 TJ Box sealing with silicon glue.

Posted onNovember 26, 2023November 26, 2023

Listen to the Message PWID52:DTW201 to 205 TJ Box sealing with silicon glue.Continue