WID600: IRP-1 & IRP-2 GCP & PLC Communication check list
SL No. DTW No. Serial Comm. Condition Generator Battery Cable Remarks 01 101 Okay Okay Okay 02 102 Okay Okay Okay …
-
-
WID597: Dtw-101 PIT value isn’t shown in SCADA .
Findings: PIT internal CKT damaged found. Action Taken: Install new pressure transmitter.
-
WID599: DTW-121 serial communication problem. Need to check.
Findings: 1. Always PWP panel inverter fault is showing. 2. Magnetic Contact coil damaged found. Action Taken: Magnetic contact change.
-
WID594: Dtw-203 Radio communication error. Need to check.
Findings: SCADAPack STAT-LED blinking in Red signal. Action Taken: Restart the SCADAPack & radio modem.
-
WID590: IRP-1 OGR utility pump problem check.IRP-1 OGR utility pump problem check.
Findings: Switch problem found. Action taken: Switch replace.
-
WID587: DTW115 GiMAC values isn’t shown in SCADA.
Findings: Communication isn’t occurred in GiMAC meter. Action taken: 1. Physically check. Checked by modbuspool. GiMAC meter comm. Port has problem. Only transmit…
-
WID590: IRP-1 OGR utility pump problem check.
Findings: Flote Switch mis-displacement problem found. Need to dressing the cable with cable tie.
-