  • ACTIVITY | DTW | Parvez | Uncategorized

    WID585:Dtw-117 e-PRV CRD isn’t functioning properly. SEL manpower need to check.Now e-PRV CRD & flowmeter works

    Posted onNovember 25, 2023November 26, 2023

    26.11.2023 Today SEL manpower change the e-PRV CRD spring. And we check the e-PRV functionality is okay or not okay. MOV-1 50% Open,…

    Listen to the Message WID585:Dtw-117 e-PRV CRD isn’t functioning properly. SEL manpower need to check.Now e-PRV CRD & flowmeter worksContinue

  • ACTIVITY | DTW | Parvez | REPORTS

    DTW-113 LIT,PIT,FIT isolation due to regeneration

    Posted onNovember 23, 2023November 25, 2023

    Unable to take LIT, due to keep heavy machinery in DTW compound. We collect Electronic PIT, Manual Pressure Gauge. And disconnect power supply…

    Listen to the Message DTW-113 LIT,PIT,FIT isolation due to regenerationContinue

  • CCTV | Parvez | REPORTS

    IRP-2 Sub-station optical fiber arrangement done.

    Posted onNovember 23, 2023November 23, 2023

    Listen to the Message IRP-2 Sub-station optical fiber arrangement done.Continue

  • CCTV | DTW | Jewel | Parvez

    WID550: DTW-207 optical fiber maintenance.

    Posted onNovember 23, 2023November 23, 2023

    Findings: Lots of hanging TJ box is visiable. Action Taken: Reduce TJ box replacing optical fiber.

    Listen to the Message WID550: DTW-207 optical fiber maintenance.Continue

  • DAILY REPORTS | DTW | Parvez

    WID577: DTW-204 ACB can not close from SCADA.

    Posted onNovember 22, 2023December 11, 2023

    Findings: UVR being under voltage, it need a reset to execute Close Command. Action: ACB open/close command relay check. Isolate the physical reset…

    Listen to the Message WID577: DTW-204 ACB can not close from SCADA.Continue

  • ACTIVITY | Parvez

    PWID106: IRP-1 All FCP & LOP panel clean.

    Posted onNovember 21, 2023November 21, 2023

    Listen to the Message PWID106: IRP-1 All FCP & LOP panel clean.Continue

  • ACTIVITY | DAILY REPORTS | MOV | Parvez | Uncategorized

    WID568: IRP-01 Sand filter MOV-2V07L MOV Opening and closing time Percent value not showing … During the Opening period Directly 0 to 100% showing. Need to check.

    Posted onNovember 21, 2023November 22, 2023

    Finding: MOV 2V07-L opening & closing time percentage isn’t showing properly in SCADA & Field side. Action Taken: Reset the MOV-2V07.

    Listen to the Message WID568: IRP-01 Sand filter MOV-2V07L MOV Opening and closing time Percent value not showing … During the Opening period Directly 0 to 100% showing. Need to check.Continue

  • DTW102 | NETWORK CONNECTIVITY | Parvez

    WID565: DTW102 Radio communication error.

    Posted onNovember 18, 2023November 18, 2023

    Findings: Antenna cable & UTP cable connection lose problem found. Action taken: 1. Turn off the radio modem. 2. Plug out all connection….

    Listen to the Message WID565: DTW102 Radio communication error.Continue

  • CCTV | NETWORK CONNECTIVITY | Parvez | REPORTS

    WID563: IRP-2 Inside 4 Nos 360 degree camera maintenance.

    Posted onNovember 16, 2023November 16, 2023

    Findings: SFP problem found in 1 Nos S-Ring switch. As a result, 172.16.100.110,111,113,115 I/P assigned camera’s view isn’t shown in SCADA monitor. Action…

    Listen to the Message WID563: IRP-2 Inside 4 Nos 360 degree camera maintenance.Continue

  • DAILY REPORTS | DTW | Parvez | REPORTS | Uncategorized

    WID562:DTW217 flow value is not shown in SCADA

    Posted onNovember 15, 2023November 16, 2023

    Findings: The cable was disconnected. Action taken: Dressing the cable and reconnect.

    Listen to the Message WID562:DTW217 flow value is not shown in SCADAContinue