DTW-101,102,104,105,107 overall system visual check.
DTW-101: 1. 2 Nos cooling fan do not work at CCTV panel. 2. LIT shows over range value. 3. Earthing bus bar panel…
DTW-101: 1. 2 Nos cooling fan do not work at CCTV panel. 2. LIT shows over range value. 3. Earthing bus bar panel…
DTW-103: 1. Need to fill breather oil in transformer. 2. UVR burned. 3. Digital PIT off. 4. 1 Nos Cooling fan off in…
Problem: 01 nos CC Camera Do not show footage in NAV.Problem found: Automatic IP has been changed in the dome Camera. Than IP…
Problem: PIT value does not showing in the SCADA & field device.Problem found: PIT 24v AC supply fuse damage found & maintenance. now…
Problem: after power up time ACB do not close from the SCADA command.Problem found: DTW 114 UVR its burn inside circuit . UVR…
Problem: after power up time ACB do not close from the SCADA command.Problem found: 27X M/C Magnetic Contact & AUX CONTACT UNIT Problem…
Problem: Shutdown time is ACB not open.Problem found: ACB Internal control unit not working found.Observation: DTW 203 UVR checked, When plug PTT UVR…
Unused & damage LIT sensor collects complete from DTW 105 – 1 nos DTW 106 – 1 nos & new lit sensor install.DTW…
Problem: This MOV is abnormal working. MOV Open time & close time 0% to 100% value not showing. IRP-2 3V07A MOV Reset, reprogramming…