DTW VISUAL CHECK REPORT

Posted onOctober 11, 2022

DTW NO. CCTV LV PWP RTU GCP 101 102 103 104 105 106 107 109 110 111 112 113 114 115 117 118…

Listen to the Message DTW VISUAL CHECK REPORTContinue

DTW-101,102,104,105,107 overall system visual check.
Uncategorized

DTW-101,102,104,105,107 overall system visual check.

Posted onOctober 11, 2022October 11, 2022

DTW-101: 1. 2 Nos cooling fan do not work at CCTV panel. 2. LIT shows over range value. 3. Earthing bus bar panel…

Listen to the Message DTW-101,102,104,105,107 overall system visual check.Continue

Uncategorized

DTW-121 Radio Signal Strength Check.

Posted onOctober 11, 2022October 11, 2022

Listen to the Message DTW-121 Radio Signal Strength Check.Continue

Uncategorized

DTW-103,106,121 over all check list.

Posted onOctober 11, 2022October 11, 2022

DTW-103: 1. Need to fill breather oil in transformer. 2. UVR burned. 3. Digital PIT off. 4. 1 Nos Cooling fan off in…

Listen to the Message DTW-103,106,121 over all check list.Continue

DTW 104 CCTV maintenance complete.
ACTIVITY | CCTV | DAILY REPORTS | DTW | Jewel

DTW 104 CCTV maintenance complete.

Posted onOctober 10, 2022October 10, 2022

Problem: 01 nos CC Camera Do not show footage in NAV.Problem found: Automatic IP has been changed in the dome Camera. Than IP…

Listen to the Message DTW 104 CCTV maintenance complete.Continue

DTW 117 PIT Checking and maintenance complete.
ACTIVITY | DAILY REPORTS | DTW | Pappu

DTW 117 PIT Checking and maintenance complete.

Posted onOctober 10, 2022October 10, 2022

Problem: PIT value does not showing in the SCADA & field device.Problem found: PIT 24v AC supply fuse damage found & maintenance. now…

Listen to the Message DTW 117 PIT Checking and maintenance complete.Continue

DTW- 114 UVR & UVR Related M/C checking complete.
ACTIVITY | DAILY REPORTS | DTW | Pappu | Pending Issue

DTW- 114 UVR & UVR Related M/C checking complete.

Posted onOctober 10, 2022October 11, 2022

Problem: after power up time ACB do not close from the SCADA command.Problem found: DTW 114 UVR its burn inside circuit . UVR…

Listen to the Message DTW- 114 UVR & UVR Related M/C checking complete.Continue

DTW- 113 UVR & UVR Related M/C checking complete.
ACTIVITY | DAILY REPORTS | DTW | Pappu | Pending Issue

DTW- 113 UVR & UVR Related M/C checking complete.

Posted onOctober 10, 2022October 11, 2022

Problem: after power up time ACB do not close from the SCADA command.Problem found: 27X M/C Magnetic Contact & AUX CONTACT UNIT Problem…

Listen to the Message DTW- 113 UVR & UVR Related M/C checking complete.Continue

DTW 203 UVR checking complete.
ACTIVITY | DAILY REPORTS | DTW | Pappu | Pending Issue

DTW 203 UVR checking complete.

Posted onOctober 10, 2022October 11, 2022

Problem: Shutdown time is ACB not open.Problem found: ACB Internal control unit not working found.Observation: DTW 203 UVR checked, When plug PTT UVR…

Listen to the Message DTW 203 UVR checking complete.Continue

Unused & damage LIT sensor collects complete   from DTW 105,106,115,203 & 212
ACTIVITY | DAILY REPORTS | DTW | Pappu

Unused & damage LIT sensor collects complete from DTW 105,106,115,203 & 212

Posted onOctober 10, 2022October 10, 2022

Unused & damage LIT sensor collects complete from DTW 105 – 1 nos DTW 106 – 1 nos & new lit sensor install.DTW…

Listen to the Message Unused & damage LIT sensor collects complete from DTW 105,106,115,203 & 212Continue