DTW VISUAL CHECK REPORT
DTW NO. CCTV LV PWP RTU GCP 101 102 103 104 105 106 107 109 110 111 112 113 114 115 117 118…
DTW NO. CCTV LV PWP RTU GCP 101 102 103 104 105 106 107 109 110 111 112 113 114 115 117 118…
DTW-101: 1. 2 Nos cooling fan do not work at CCTV panel. 2. LIT shows over range value. 3. Earthing bus bar panel…
DTW-103: 1. Need to fill breather oil in transformer. 2. UVR burned. 3. Digital PIT off. 4. 1 Nos Cooling fan off in…
Problem: 01 nos CC Camera Do not show footage in NAV.Problem found: Automatic IP has been changed in the dome Camera. Than IP…
Problem: PIT value does not showing in the SCADA & field device.Problem found: PIT 24v AC supply fuse damage found & maintenance. now…
Problem: after power up time ACB do not close from the SCADA command.Problem found: DTW 114 UVR its burn inside circuit . UVR…
Problem: after power up time ACB do not close from the SCADA command.Problem found: 27X M/C Magnetic Contact & AUX CONTACT UNIT Problem…
Problem: Shutdown time is ACB not open.Problem found: ACB Internal control unit not working found.Observation: DTW 203 UVR checked, When plug PTT UVR…
Unused & damage LIT sensor collects complete from DTW 105 – 1 nos DTW 106 – 1 nos & new lit sensor install.DTW…