  • DTW- 113 UVR & UVR Related M/C checking complete.
    ACTIVITY | DAILY REPORTS | DTW | Pappu | Pending Issue

    DTW- 113 UVR & UVR Related M/C checking complete.

    Posted onOctober 10, 2022October 11, 2022

    Problem: after power up time ACB do not close from the SCADA command.Problem found: 27X M/C Magnetic Contact & AUX CONTACT UNIT Problem…

    Listen to the Message DTW- 113 UVR & UVR Related M/C checking complete.Continue

  • DTW 203 UVR checking complete.
    ACTIVITY | DAILY REPORTS | DTW | Pappu | Pending Issue

    DTW 203 UVR checking complete.

    Posted onOctober 10, 2022October 11, 2022

    Problem: Shutdown time is ACB not open.Problem found: ACB Internal control unit not working found.Observation: DTW 203 UVR checked, When plug PTT UVR…

    Listen to the Message DTW 203 UVR checking complete.Continue

  • Unused & damage LIT sensor collects complete   from DTW 105,106,115,203 & 212
    ACTIVITY | DAILY REPORTS | DTW | Pappu

    Unused & damage LIT sensor collects complete from DTW 105,106,115,203 & 212

    Posted onOctober 10, 2022October 10, 2022

    Unused & damage LIT sensor collects complete from DTW 105 – 1 nos DTW 106 – 1 nos & new lit sensor install.DTW…

    Listen to the Message Unused & damage LIT sensor collects complete from DTW 105,106,115,203 & 212Continue

  • IRP-2 3V07A MOV Reset, reprogramming and configuration work complete.
    ACTIVITY | DAILY REPORTS | MOV | Pappu | Parvez

    IRP-2 3V07A MOV Reset, reprogramming and configuration work complete.

    Posted onOctober 6, 2022October 6, 2022

    Problem: This MOV is abnormal working. MOV Open time & close time 0% to 100% value not showing. IRP-2 3V07A MOV Reset, reprogramming…

    Listen to the Message IRP-2 3V07A MOV Reset, reprogramming and configuration work complete.Continue

  • Radio communication checking complete DTW 221.
    ACTIVITY | DAILY REPORTS | DTW | NETWORK CONNECTIVITY | Pappu | Pending Issue

    Radio communication checking complete DTW 221.

    Posted onOctober 6, 2022October 12, 2022

    Observation: Radio communication checking complete DTW 221.1. In DTW 221, We checked up to 10 minutes. RSSI Value (Dc volts) MAX: 2.700V, MIN:…

    Listen to the Message Radio communication checking complete DTW 221.Continue

  • Radio communication checking complete DTW 213.
    ACTIVITY | DAILY REPORTS | DTW | NETWORK CONNECTIVITY | Pappu | Pending Issue

    Radio communication checking complete DTW 213.

    Posted onOctober 6, 2022October 12, 2022

    Observation: Radio communication checking complete DTW 213.1. In DTW 213, We checked up to 10 minutes. RSSI Value (Dc volts) MAX: 2.395V, MIN:…

    Listen to the Message Radio communication checking complete DTW 213.Continue

  • UVR checking complete at DTW 216
    ACTIVITY | DAILY REPORTS | DTW | Pappu | Pending Issue

    UVR checking complete at DTW 216

    Posted onOctober 6, 2022October 12, 2022

    Problem: Shutdown time is ACB not open.Problem found: ACB Internal control unit not working found.Observation: DTW 216 UVR checked, when plug PTT UVR…

    Listen to the Message UVR checking complete at DTW 216Continue

  • ACTIVITY | DTW | Jewel | Pappu | Parvez

    CCTV camera maintenance & optical fiber rearrangement at DTW-117

    Posted onOctober 6, 2022October 6, 2022

    In DTW-117, there are 2 Nos maintenance and installation : 1. Optical fiber rearrangement. 2. 2 Nos new camera install. 3. 44 meter…

    Listen to the Message CCTV camera maintenance & optical fiber rearrangement at DTW-117Continue

  • CCTV maintenance at DTW-103
    ACTIVITY | CCTV | DTW | Jewel | Parvez

    CCTV maintenance at DTW-103

    Posted onOctober 6, 2022October 6, 2022

    In DTW-103, there are 3 Nos maintenance and installation : 1. IP configure in CCTV camera. 2. 2 Nos new camera install. 3….

    Listen to the Message CCTV maintenance at DTW-103Continue

  • DTW- 201 Radio Communication checking complete.
    ACTIVITY | DAILY REPORTS | DTW | NETWORK CONNECTIVITY | Pappu | Pending Issue

    DTW- 201 Radio Communication checking complete.

    Posted onOctober 6, 2022October 12, 2022

    Observation: DTW 201 Radio Communication checking complete. This DTWs communication is very bad.1. In DTW 201, We checked up to 10 minutes. In…

    Listen to the Message DTW- 201 Radio Communication checking complete.Continue