WID600: IRP-1 & IRP-2 GCP & PLC Communication check list
SL No. DTW No. Serial Comm. Condition Generator Battery Cable Remarks 01 101 Okay Okay Okay 02 102 Okay Okay Okay …
WID597: Dtw-101 PIT value isn’t shown in SCADA .
Findings: PIT internal CKT damaged found. Action Taken: Install new pressure transmitter.
WID599: DTW-121 serial communication problem. Need to check.
Findings: 1. Always PWP panel inverter fault is showing. 2. Magnetic Contact coil damaged found. Action Taken: Magnetic contact change.
Field Pump Checking & Maintenance.
Checking and maintenance of 2 field pumps completed.
WID594: Dtw-203 Radio communication error. Need to check.
Findings: SCADAPack STAT-LED blinking in Red signal. Action Taken: Restart the SCADAPack & radio modem.
DTW-218 UPS Output Voltage Showing High.
New UPS installed at DTW-218 and old UPS brought to plant for problem checking. Now the pump is running and everything is normal.