	WID594: Dtw-203 Radio communication error. Need to check.Findings: SCADAPack STAT-LED blinking in Red signal. Action Taken: Restart the SCADAPack & radio modem. 
- 
	DTW-218 UPS Output Voltage Showing High.New UPS installed at DTW-218 and old UPS brought to plant for problem checking. Now the pump is running and everything is normal. 
- 
	IRP#01 Main substation, Electrical Panel Room, OGR Electrical Panel Room Cleaning & Visual Check.IRP#01 Main substation, Electrical Panel Room, OGR Electrical Panel Room Cleaning & Visual Check Work Completed. 
- 
	
- 
	OGR Panel Room AC Cold Air Does Not Come Out.AC Problem solved & Running. The functions of the remote cannot be changed. AC will automatically change after 6 hours. Everything has been… 
- 
	
- 
	
- 
	WID590: IRP-1 OGR utility pump problem check.IRP-1 OGR utility pump problem check.Findings: Switch problem found. Action taken: Switch replace. 
- 
	WID587: DTW115 GiMAC values isn’t shown in SCADA.Findings: Communication isn’t occurred in GiMAC meter. Action taken: 1. Physically check. Checked by modbuspool. GiMAC meter comm. Port has problem. Only transmit… 