DTW- 114 UVR & UVR Related M/C checking complete.
Problem: after power up time ACB do not close from the SCADA command.Problem found: DTW 114 UVR its burn inside circuit . UVR…
-
ACTIVITY | DAILY REPORTS | DTW | Pappu | Pending Issue
DTW- 113 UVR & UVR Related M/C checking complete.
Problem: after power up time ACB do not close from the SCADA command.Problem found: 27X M/C Magnetic Contact & AUX CONTACT UNIT Problem…
-
ACTIVITY | DAILY REPORTS | DTW | Pappu | Pending Issue
DTW 203 UVR checking complete.
Problem: Shutdown time is ACB not open.Problem found: ACB Internal control unit not working found.Observation: DTW 203 UVR checked, When plug PTT UVR…
-
Radio communication checking complete DTW 221.
Observation: Radio communication checking complete DTW 221.1. In DTW 221, We checked up to 10 minutes. RSSI Value (Dc volts) MAX: 2.700V, MIN:…
-
Radio communication checking complete DTW 213.
Observation: Radio communication checking complete DTW 213.1. In DTW 213, We checked up to 10 minutes. RSSI Value (Dc volts) MAX: 2.395V, MIN:…
-
ACTIVITY | DAILY REPORTS | DTW | Pappu | Pending Issue
UVR checking complete at DTW 216
Problem: Shutdown time is ACB not open.Problem found: ACB Internal control unit not working found.Observation: DTW 216 UVR checked, when plug PTT UVR…