SL NO | Parameter | Description |
---|---|---|
1 | Range of product | Modicon M221 |
2 | Product or component type | Logic controller |
3 | [Us] rated supply voltage | 100…240 V AC |
4 | discrete input number | 14, discrete input conforming to IEC 61131-2 Type 1 |
5 | analogue input number | 2 at 0…10 V |
6 | Discrete output type | Relay normally open |
7 | discrete output number | 10 relay |
8 | discrete output voltage | 5…125 V DC 5…250 V AC |
9 | discrete output current | 2 A |
10 | Discrete I/O number | 24 |
11 | maximum number of I/O expansion module | 7 for transistor output 7 for relay output |
12 | Supply voltage limits | 85…264 V |
13 | Network frequency | 50/60 Hz |
14 | Inrush current | 40 A |
15 | maximum power consumption in VA | 58 VA at 100…240 V with max number of I/O expansion module 35 VA at 100…240 V without I/O expansion module |
16 | power supply output current | 0.52 A 5 V for expansion bus 0.16 A 24 V for expansion bus |
17 | discrete input logic | Sink or source (positive/negative) |
18 | Discrete input voltage | 24 V |
19 | Discrete input voltage type | DC |
20 | Analogue input resolution | 10 bits |
21 | LSB value | 10 mV |
22 | conversion time | 1 ms per channel + 1 controller cycle time for analogue input analog input |
23 | permitted overload on inputs | +/- 30 V DC for 5 min (maximum) for analog input +/- 13 V DC (permanent) for analog input |
24 | voltage state 1 guaranteed | >= 15 V for input |
25 | voltage state 0 guaranteed | <= 5 V for input |
26 | discrete input current | 7 mA for discrete input 5 mA for fast input |
27 | input impedance | 3.4 kOhm for discrete input 100 kOhm for analog input 4.9 kOhm for fast input |
28 | response time | 35 µs turn-off, I2…I5 terminal(s) for input 10 ms turn-on for output 10 ms turn-off for output 5 µs turn-on, I0, I1, I6, I7 terminal(s) for fast input 35 µs turn-on, other terminals terminal(s) for input 5 µs turn-off, I0, I1, I6, I7 terminal(s) for fast input 100 µs turn-off, other terminals terminal(s) for input |
29 | configurable filtering time | 0 ms for input 3 ms for input 12 ms for input |
30 | output voltage limits | 125 V DC 277 V AC |
31 | maximum current per output common | 4 A at COM 2 7 A at COM 0 7 A at COM 1 |
32 | absolute accuracy error | +/- 1 % of full scale for analog input |
33 | electrical durability | 100000 cycles AC-12, 120 V, 240 VA, resistive 100000 cycles AC-12, 240 V, 480 VA, resistive 300000 cycles AC-12, 120 V, 80 VA, resistive 300000 cycles AC-12, 240 V, 160 VA, resistive 100000 cycles AC-15, cos phi = 0.35, 120 V, 60 VA, inductive 100000 cycles AC-15, cos phi = 0.35, 240 V, 120 VA, inductive 300000 cycles AC-15, cos phi = 0.35, 120 V, 18 VA, inductive 300000 cycles AC-15, cos phi = 0.35, 240 V, 36 VA, inductive 100000 cycles AC-14, cos phi = 0.7, 120 V, 120 VA, inductive 100000 cycles AC-14, cos phi = 0.7, 240 V, 240 VA, inductive 300000 cycles AC-14, cos phi = 0.7, 120 V, 36 VA, inductive 300000 cycles AC-14, cos phi = 0.7, 240 V, 72 VA, inductive 100000 cycles DC-12, 24 V, 48 W, resistive 300000 cycles DC-12, 24 V, 16 W, resistive 100000 cycles DC-13, 24 V, 24 W, inductive (L/R = 7 ms) 300000 cycles DC-13, 24 V, 7.2 W, inductive (L/R = 7 ms) |
34 | switching frequency | 20 switching operations/minute with maximum load |
35 | mechanical durability | 20000000 cycles for relay output |
36 | minimum load | 1 mA at 5 V DC for relay output |
37 | protection type | Without protection at 5 A |
38 | reset time | 1 s |
39 | memory capacity | 256 kB for user application and data RAM with 10000 instructions 256 kB for internal variables RAM |
40 | data backed up | 256 kB built-in flash memory for backup of application and data |
41 | data storage equipment | 2 GB SD card (optional) |
42 | battery type | BR2032 lithium non-rechargeable, battery life: 4 year(s) |
43 | backup time | 1 year at 25 °C (by interruption of power supply) |
44 | execution time for 1 KInstruction | 0.3 ms for event and periodic task |
45 | execution time per instruction | 0.2 µs Boolean |
46 | exct time for event task | 60 µs response time |
47 | Maximum size of object areas | 255 %TM timers 512 %M memory bits 8000 %MW memory words 255 %C counters 512 %KW constant words |
48 | Realtime clock | With |
49 | clock drift | <= 30 s/month at 25 °C |
50 | regulation loop | Adjustable PID regulator up to 14 simultaneous loops |
51 | counting input number | 4 fast input (HSC mode) at 100 kHz 32 bits |
52 | counter function | A/B Single phase Pulse/direction |
53 | integrated connection type | USB port with mini B USB 2.0 connector Non isolated serial link serial 1 with RJ45 connector and RS232/RS485 interface Ethernet with RJ45 connector |
54 | supply | (Serial)serial link supply: 5 V, <200 mA |
55 | transmission rate | 1.2…115.2 kbit/s (115.2 kbit/s by default) for bus length of 15 m for RS485 1.2…115.2 kbit/s (115.2 kbit/s by default) for bus length of 3 m for RS232 480 Mbit/s for USB |
56 | communication port protocol | USB port: USB – SoMachine-Network Non isolated serial link: Modbus master/slave – RTU/ASCII or SoMachine-Network Ethernet |
57 | port Ethernet | 10BASE-T/100BASE-TX 1 port with 100 m copper cable |
58 | Communication service | Modbus TCP server Modbus TCP slave device DHCP client Modbus TCP client Ethernet/IP adapter |
59 | local signalling | 1 LED (green) for PWR 1 LED (green) for RUN 1 LED (red) for module error (ERR) 1 LED (green) for SD card access (SD) 1 LED (red) for BAT 1 LED per channel (green) for I/O state 1 LED (green) for SL Ethernet network activity (green) for ACT Ethernet network link (yellow) for Link (Link Status) |
60 | electrical connection | Removable screw terminal block for inputs removable screw terminal block for outputs terminal block, 3 terminal(s) for connecting the 24 V DC power supply connector, 4 terminal(s) for analogue inputs Mini B USB 2.0 connector for a programming terminal |
61 | maximum cable distance between devices | Shielded cable: <10 m for fast input Unshielded cable: <30 m for output Unshielded cable: <30 m for digital input Unshielded cable: <1 m for analog input |
62 | insulation | Between input and internal logic at 500 V AC Non-insulated between analogue input and internal logic Non-insulated between analogue inputs Between supply and ground at 1500 V AC Between sensor power supply and ground at 500 V AC Between input and ground at 500 V AC Between output and ground at 1500 V AC Between supply and internal logic at 2300 V AC Between sensor power supply and internal logic at 500 V AC Between output and internal logic at 2300 V AC Between Ethernet terminal and internal logic at 500 V AC Between supply and sensor power supply at 2300 V AC |
63 | Marking | CE |
64 | sensor power supply | 24 V DC at 250 mA supplied by the controller |
65 | mounting support | Top hat type TH35-15 rail conforming to IEC 60715 Top hat type TH35-7.5 rail conforming to IEC 60715 plate or panel with fixing kit |
66 | Height | 90 mm |
67 | Depth | 70 mm |
68 | Width | 110 mm |
69 | Net weight | 0.395 kg |
70 | Standards | EN/IEC 61010-2-201 EN/IEC 61131-2 EN/IEC 60664-1 |
71 | Product certifications | LR cULus IACS E10 CSA ABS DNV-GL EAC RCM |
72 | Environmental characteristic | Ordinary and hazardous location |
73 | resistance to electrostatic discharge | 8 kV in air conforming to EN/IEC 61000-4-2 4 kV on contact conforming to EN/IEC 61000-4-2 |
74 | resistance to electromagnetic fields | 10 V/m 80 MHz…1 GHz conforming to EN/IEC 61000-4-3 3 V/m 1.4 GHz…2 GHz conforming to EN/IEC 61000-4-3 1 V/m 2…2.7 GHz conforming to EN/IEC 61000-4-3 |
75 | resistance to magnetic fields | 30 A/m 50/60 Hz conforming to EN/IEC 61000-4-8 |
76 | resistance to fast transients | 2 kV (power lines) conforming to EN/IEC 61000-4-4 2 kV (relay output) conforming to EN/IEC 61000-4-4 1 kV (I/O) conforming to EN/IEC 61000-4-4 1 kV (Ethernet line) conforming to EN/IEC 61000-4-4 1 kV (serial link) conforming to EN/IEC 61000-4-4 |
77 | surge withstand | 2 kV power lines (AC) common mode conforming to EN/IEC 61000-4-5 2 kV relay output common mode conforming to EN/IEC 61000-4-5 1 kV I/O common mode conforming to EN/IEC 61000-4-5 1 kV shielded cable common mode conforming to EN/IEC 61000-4-5 0.5 kV power lines (DC) differential mode conforming to EN/IEC 61000-4-5 1 kV power lines (AC) differential mode conforming to EN/IEC 61000-4-5 1 kV relay output differential mode conforming to EN/IEC 61000-4-5 0.5 kV power lines (DC) common mode conforming to EN/IEC 61000-4-5 |
78 | resistance to conducted disturbances | 10 V 0.15…80 MHz conforming to EN/IEC 61000-4-6 3 V 0.1…80 MHz conforming to Marine specification (LR, ABS, DNV, GL) 10 V spot frequency (2, 3, 4, 6.2, 8.2, 12.6, 16.5, 18.8, 22, 25 MHz) conforming to Marine specification (LR, ABS, DNV, GL) |
79 | electromagnetic emission | Conducted emissions – test level: 79 dBμV/m QP/66 dBμV/m AV ( power lines (AC)) at 0.15…0.5 MHz conforming to EN/IEC 55011 Conducted emissions – test level: 73 dBμV/m QP/60 dBμV/m AV ( power lines (AC)) at 0.5…300 MHz conforming to EN/IEC 55011 Conducted emissions – test level: 120…69 dBµV/m QP ( power lines) at 10…150 kHz conforming to EN/IEC 55011 Conducted emissions – test level: 63 dBμV/m QP ( power lines) at 1.5…30 MHz conforming to EN/IEC 55011 Radiated emissions – test level: 40 dBμV/m QP class A ( 10 m) at 30…230 MHz conforming to EN/IEC 55011 Conducted emissions – test level: 79…63 dBμV/m QP ( power lines) at 150…1500 kHz conforming to EN/IEC 55011 Radiated emissions – test level: 47 dBμV/m QP class A ( 10 m) at 200…1000 MHz conforming to EN/IEC 55011 |
80 | Immunity to microbreaks | 10 ms |
81 | ambient air temperature for operation | -10…55 °C (horizontal installation) -10…35 °C (vertical installation) |
82 | Ambient air temperature for storage | -25…70 °C |
83 | relative humidity | 10…95 %, without condensation (in operation) 10…95 %, without condensation (in storage) |
84 | IP degree of protection | IP20 with protective cover in place |
85 | Pollution degree | <= 2 |
86 | Operating altitude | 0…2000 m |
87 | Storage altitude | 0…3000 m |
88 | vibration resistance | 3.5 mm at 5…8.4 Hz on symmetrical rail 3.5 mm at 5…8.4 Hz on panel mounting 1 gn at 8.4…150 Hz on symmetrical rail 1 gn at 8.4…150 Hz on panel mounting |
89 | shock resistance | 98 m/s² for 11 ms |