PIT maintenance work report
Dtw-213 maintenance. Now ok
Dtw-208 maintenance
Now ok
Dtw-207 maintenance
Now ok
Dtw-211 PIT damaged
Dtw-203 PIT doesn’t exist.
Dtw-205 PIT damaged
Dtw-206 SCADA PACK doesn’t exist
PIT maintenance work report
Dtw-213 maintenance. Now ok
Dtw-208 maintenance
Now ok
Dtw-207 maintenance
Now ok
Dtw-211 PIT damaged
Dtw-203 PIT doesn’t exist.
Dtw-205 PIT damaged
Dtw-206 SCADA PACK doesn’t exist
DTW-211 CCTV power is taken from main ups. Do not get sufficient backup from ups and frequently fault occurs.
IRP-2 RTU Panel, Server Panel & VFD Panel Cleaning Done
Dtw 101,102,103,109,110 RTU panel , VFD internal site & CCTV panel cleaning complete .
Problem: PIT value does not showing in the SCADA & field device.Problem found: PIT 24v AC supply fuse damage found & maintenance. now…
Observation: Radio communication checking complete DTW 221.1. In DTW 221, We checked up to 10 minutes. RSSI Value (Dc volts) MAX: 2.700V, MIN:…