  • ACTIVITY | DTW | Parvez | REPORTS

    DTW-113 LIT,PIT,FIT isolation due to regeneration

    Posted onNovember 23, 2023November 25, 2023

    Unable to take LIT, due to keep heavy machinery in DTW compound. We collect Electronic PIT, Manual Pressure Gauge. And disconnect power supply…

    Listen to the Message DTW-113 LIT,PIT,FIT isolation due to regenerationContinue

  • CCTV | Parvez | REPORTS

    IRP-2 Sub-station optical fiber arrangement done.

    Posted onNovember 23, 2023November 23, 2023

    Listen to the Message IRP-2 Sub-station optical fiber arrangement done.Continue

  • CCTV | DTW | Jewel | Parvez

    WID550: DTW-207 optical fiber maintenance.

    Posted onNovember 23, 2023November 23, 2023

    Findings: Lots of hanging TJ box is visiable. Action Taken: Reduce TJ box replacing optical fiber.

    Listen to the Message WID550: DTW-207 optical fiber maintenance.Continue

  • DAILY REPORTS | DTW | Parvez

    WID577: DTW-204 ACB can not close from SCADA.

    Posted onNovember 22, 2023December 11, 2023

    Findings: UVR being under voltage, it need a reset to execute Close Command. Action: ACB open/close command relay check. Isolate the physical reset…

    Listen to the Message WID577: DTW-204 ACB can not close from SCADA.Continue

  • ACTIVITY | DAILY REPORTS | MOV | Parvez | Uncategorized

    WID568: IRP-01 Sand filter MOV-2V07L MOV Opening and closing time Percent value not showing … During the Opening period Directly 0 to 100% showing. Need to check.

    Posted onNovember 21, 2023November 22, 2023

    Finding: MOV 2V07-L opening & closing time percentage isn’t showing properly in SCADA & Field side. Action Taken: Reset the MOV-2V07.

    Listen to the Message WID568: IRP-01 Sand filter MOV-2V07L MOV Opening and closing time Percent value not showing … During the Opening period Directly 0 to 100% showing. Need to check.Continue

  • CCTV | NETWORK CONNECTIVITY | Parvez | REPORTS

    WID563: IRP-2 Inside 4 Nos 360 degree camera maintenance.

    Posted onNovember 16, 2023November 16, 2023

    Findings: SFP problem found in 1 Nos S-Ring switch. As a result, 172.16.100.110,111,113,115 I/P assigned camera’s view isn’t shown in SCADA monitor. Action…

    Listen to the Message WID563: IRP-2 Inside 4 Nos 360 degree camera maintenance.Continue

  • DAILY REPORTS | DTW | Parvez | REPORTS | Uncategorized

    WID562:DTW217 flow value is not shown in SCADA

    Posted onNovember 15, 2023November 16, 2023

    Findings: The cable was disconnected. Action taken: Dressing the cable and reconnect.

    Listen to the Message WID562:DTW217 flow value is not shown in SCADAContinue

  • DTW-122 Grass plantation
    ACTIVITY | DAILY REPORTS | DTW | Jewel | Parvez | REPORTS

    DTW-122 Grass plantation

    Posted onDecember 22, 2022December 22, 2022

    There is so much dust  so we Plant grass to prevent road side dust

    Listen to the Message DTW-122 Grass plantationContinue

  • IRP-2 All Dome Camera Lens Cleaning
    ACTIVITY | DAILY REPORTS | Jewel | Parvez | REPORTS

    IRP-2 All Dome Camera Lens Cleaning

    Posted onDecember 21, 2022December 21, 2022

    IRP-2 All Dome Camera Lens Cleaning Done

    Listen to the Message IRP-2 All Dome Camera Lens CleaningContinue

  • SCADA Room & Work Station CPU cleaning
    ACTIVITY | DAILY REPORTS | Jewel | Parvez | REPORTS

    SCADA Room & Work Station CPU cleaning

    Posted onDecember 21, 2022December 21, 2022

    SCADA Room & Work Station CPU cleaning

    Listen to the Message SCADA Room & Work Station CPU cleaningContinue