WID577: DTW-204 ACB can not close from SCADA.
Findings: UVR being under voltage, it need a reset to execute Close Command. Action: ACB open/close command relay check. Isolate the physical reset…
Findings: UVR being under voltage, it need a reset to execute Close Command. Action: ACB open/close command relay check. Isolate the physical reset…
Finding: MOV 2V07-L opening & closing time percentage isn’t showing properly in SCADA & Field side. Action Taken: Reset the MOV-2V07.
Findings: The cable was disconnected. Action taken: Dressing the cable and reconnect.
 
			There is so much dust so we Plant grass to prevent road side dust
 
			IRP-2 All Dome Camera Lens Cleaning Done
 
			SCADA Room & Work Station CPU cleaning
 
			DTW-101,102,103,104,107,109,110,111,209,206,207,205,208,203,201 Camera Lens Cleaning Done There are too much dust accumulate on the camera lens and the video footage isn’t clear to understand.
 
			DTW-120 CCTV Maintenance There was connector Problem. Now DTW-120 (5 nos ) camera operation in NAV-2
 
			There was so much dust
 
			CCTV modification work for Dual power source Done Now CCTV continuous View remain All time.