Findings: UVR being under voltage, it need a reset to execute Close Command.
Action: ACB open/close command relay check. Isolate the physical reset cable from MC.






Findings: UVR being under voltage, it need a reset to execute Close Command.
Action: ACB open/close command relay check. Isolate the physical reset cable from MC.






Observation: Radio communication checking complete DTW 213.1. In DTW 213, We checked up to 10 minutes. RSSI Value (Dc volts) MAX: 2.395V, MIN:…
Problem: after power up time ACB do not close from the SCADA command.Problem found: 27X M/C Magnetic Contact & AUX CONTACT UNIT Problem…
IRP-1 All sandfilter ultrasonic sensor cleaning Done. There was so much dust
DTW-104,105,106,107 Cleaning Done
DTW-211 CCTV power is taken from main ups. Do not get sufficient backup from ups and frequently fault occurs.
IRP-1 CCTV monitor HDMI cable plug & power up Done