ACTIVITY | DAILY REPORTS | Parvez | REPORTSOGR Booster room dewatering pump run command showing problem at low level
Posted onFloat switch reconnection and rearrange. Now normal
ACTIVITY | DAILY REPORTS | Pappu | ParvezIRP-2 Sludge Drying Bed Pump-A Float Type Level Sensor Maintenance
Posted onProblem: SCADA always showing HI signal. Problem found: 1 NOS float switch problem found. A good sensor in HIHI position is replaced with…
ACTIVITY | DAILY REPORTS | DTW | Pappu | ParvezDTW-110 Pump inspection & ready to run up.
Posted onProblem Found: 1. VFD (-) Hz showing 2. Non-return Valve damaged. 3. Reverse water flow. 4. The pump acts as a generator due…
ACTIVITY | DAILY REPORTS | Jewel | Parvez | REPORTSIRP-2 Sub-Station Re cleaning
Posted onThere was so much dust