    DTW’S PRESSURE INDICATOR TRANSMITTER REPORT

    Posted onSeptember 24, 2022September 24, 2022

    SAVAR-KERANIGANJ WELL FIELD PLANT DTW,S PRESSURE INDICATOR TRANSMITTER REPORT (24.09.2022) DTW NO. VALUE STATUS DTW NO. VALUE STATUS 101 2.3  OK 201 1.9…

    Listen to the Message DTW’S PRESSURE INDICATOR TRANSMITTER REPORTContinue

  • ACTIVITY | DAILY REPORTS | DTW | Pending Issue

    DTW-117 & 118 UVR Related M/C checking.

    Posted onSeptember 22, 2022October 12, 2022

    Problem: after power up time ACB do not close from the SCADA command. Problem found: 27X Magnetic Contact (M/C) & AUX Contact Unit…

    Listen to the Message DTW-117 & 118 UVR Related M/C checking.Continue

  • ACTIVITY | Product Specifications

    CL2 INSTRUMENT LIST

    Posted onSeptember 22, 2022September 28, 2022

    CL2 INSTRUMENT LIST SL NO Product Name Model Brand Panel Power Meter KDX-AC Light Star Top Touch Operation Panel XTOP12TS M2I Corporation Gas…

    Listen to the Message CL2 INSTRUMENT LISTContinue

  • ACTIVITY | DAILY REPORTS | Pending Issue

    OGR Booster pump E checking & maintenance.

    Posted onSeptember 22, 2022October 12, 2022

    Problem: OGR Booster pump E running time Moter current high (682 Amp) showing than pump stop that time frequency is 0.3 Hz (Abnormal).Problem…

    Listen to the Message OGR Booster pump E checking & maintenance.Continue

  • ACTIVITY | CCTV | DAILY REPORTS | DTW

    DTW-201 CCTV checking

    Posted onSeptember 22, 2022September 26, 2022

    Problem: Do not show footage in NAV.Problem found: ONU & 1 Nos cc camera Problem found.

    Listen to the Message DTW-201 CCTV checkingContinue

  • ACTIVITY

    Equipment’s List for SKWP[Location Wise]

    Posted onSeptember 22, 2022November 5, 2022

    Table of Contents DTW SCADA PANEL ROOM OGR ELECTRICAL PANEL ROOM SAND FILTER ELECTRICAL PANEL ROOM DOME CAMERA PANEL DTW SL NO Item…

    Listen to the Message Equipment’s List for SKWP[Location Wise]Continue

  • ACTIVITY | DAILY REPORTS

    4 nos Monitoring Well Level Sensor Installation Complete.

    Posted onSeptember 21, 2022September 21, 2022

    1 :MW03B 2: MW14A 3:MW08A 4: MW13B

    Listen to the Message 4 nos Monitoring Well Level Sensor Installation Complete.Continue

  • Uncategorized

    DTW 223 CCTV PILLAR ARRANGEMENT & CABLING WORK COMPLETE

    Posted onSeptember 19, 2022September 19, 2022

    Listen to the Message DTW 223 CCTV PILLAR ARRANGEMENT & CABLING WORK COMPLETEContinue

  • Uncategorized

    DTW#223 CCTV

    Posted onSeptember 19, 2022September 19, 2022

    Listen to the Message DTW#223 CCTVContinue

  • ACTIVITY | DAILY REPORTS

    OGR booster pump D winding temperature & Bearing temperature sensor checking.

    Posted onSeptember 18, 2022September 18, 2022

    Problem: In those sensors, high temperature shows in transmitter display. But when we check the mA current of sensor signal, that was OK….

    Listen to the Message OGR booster pump D winding temperature & Bearing temperature sensor checking.Continue