ACTIVITY | DAILY REPORTS | DTW | Pappu | Pending IssueUVR checking complete at DTW 216
Posted onProblem: Shutdown time is ACB not open.Problem found: ACB Internal control unit not working found.Observation: DTW 216 UVR checked, when plug PTT UVR…
ACTIVITY | DAILY REPORTS | Jewel | Parvez | REPORTSSCADA Room & Work Station CPU cleaning
Posted onSCADA Room & Work Station CPU cleaning
MOV REPORT 2022
Posted onMOV Report 2022 November IRP1 SL NO MOV ID Status Remarks 1 2V03A ✅OK 2 2V03B ✅OK 3 2V03C ✅OK 4 2V03D ✅OK…
CCTV Maintenance At DTW-219
Posted on1 new camera installation 2. UTP cable change 3. Connector change 4. IP Setting 5. IP Seating
ACTIVITY | DAILY REPORTS | Jewel | Pappu | ParvezOGR booster pump D winding temperature & Bearing temperature sensor checking.
Posted onProblem: In those sensors, high temperature shows in transmitter display. But when we check the mA current of sensor signal, that was OK….
ACTIVITY | DAILY REPORTS | Jewel | Pappu | Pending IssueIRP1 Sludge drying bed float switch checking.
Posted onProblem found: Sludge bed চেম্বারে কাদার পরিমান বেশি হওয়ার কারনে ৷ LoLo সিগনালের ফ্লোট সুইচটি কাদার মধ্যে অাটকে যাচ্ছে ৷তাই স্কাডাতে HiHiLoLo সিগনাল…